General Data - Ceiling Concealed FCU (3 rows coil) | |||||||||||
50 / 60 Hz | |||||||||||
Model | FC | 200D | 300D | 400D | 500D | 600D | 800D | 1000D | 1200D | 1400D | |
Air Flow | High | CMH | 350 | 520 | 680 | 850 | 1030 | 1360 | 1700 | 2040 | 2380 |
CFM | 206 | 306 | 400 | 500 | 606 | 800 | 1000 | 1200 | 1400 | ||
Medium | CMH | 280 | 440 | 560 | 700 | 870 | 1255 | 1450 | 1830 | 2100 | |
CFM | 165 | 259 | 329 | 412 | 512 | 738 | 853 | 1076 | 1235 | ||
Low | CMH | 230 | 350 | 410 | 570 | 740 | 1080 | 1160 | 1500 | 1650 | |
CFM | 135 | 206 | 241 | 335 | 435 | 635 | 682 | 882 | 971 | ||
Total Cooling Capacity | High | W | 1970 | 2850 | 3600 | 4500 | 5400 | 7200 | 9000 | 10800 | 12600 |
Medium | W | 1780 | 2480 | 3250 | 3860 | 4820 | 6780 | 8150 | 9400 | 10080 | |
Low | W | 1460 | 2050 | 2655 | 3225 | 4455 | 6200 | 7760 | 8710 | 9210 | |
Sensible Cooling Capacity | High | W | 1530 | 2190 | 2790 | 3515 | 4160 | 5600 | 7000 | 8445 | 9610 |
Medium | W | 1390 | 1980 | 2490 | 2995 | 3830 | 5185 | 6290 | 7385 | 7690 | |
Low | W | 1240 | 1610 | 2010 | 2485 | 3400 | 4810 | 6020 | 6810 | 7050 | |
Heating Capacity | High | W | 3200 | 4500 | 5000 | 6800 | 9000 | 10800 | 13500 | 16200 | 18900 |
Fan | Type | Centrifugal (Blade:Forward-Curved) | |||||||||
Quantity | 2 | 2 | 2 | 2 | 3 | 3 | 4 | 4 | 4 | ||
Motor | Type | Split-capacitor motor with ball bearing | |||||||||
Insulation Class | Class B | ||||||||||
Power Supply | V/Ph/Hz | 220~240/1/50~60 | |||||||||
Rated Power Input | High | W | 37 | 52 | 62 | 76 | 98 | 134 | 152 | 189 | 228 |
Coil | Type | Seamless copper tube mechanically bonded to aluminum hydrophili n | |||||||||
Max. Working Pressure MPa | 1,6 | ||||||||||
Pipe Connection | Rc3/4 (Female Threaded) | ||||||||||
Water Flow Rate | kg/h | 340 | 490 | 645 | 780 | 925 | 1235 | 1550 | 1850 | 2160 | |
Water Pressure Drop | kPa | 12 | 14 | 22 | 26 | 15 | 20 | 20 | 24 | 29 | |
Net Weight | kg | 25 | 25 | 25 | 25 | 40 | 40 | 45 | 45 | 45 | |
Dimension | Length | mm | 905 | 905 | 905 | 905 | 1288 | 1288 | 1672 | 1672 | 1672 |
Width | mm | 243 | 243 | 243 | 243 | 243 | 243 | 243 | 243 | 243 | |
Height | mm | 673 | 673 | 673 | 673 | 673 | 673 | 673 | 673 | 673 | |
Sound Pressure Level | dB(A) | 37 | 39 | 41 | 43 | 45 | 46 | 48 | 50 | 52 | |
Condensate Drain Size | mm | 25 | |||||||||
Note: | |||||||||||
1. Cooling and heating capacity is tested in accordance to GB/T19232-2003. | |||||||||||
2. Cooling capacity is based on the following: | |||||||||||
a)Water temperature : 7°C (inlet)/12°C (outlet) | |||||||||||
b)Air entering condition : 27°C DB/19.5°C WB | |||||||||||
3. Heating capacity is based on the following (with same water ow rate as cooling cycle): |